Frenic Ace

When the carrier frequency (F26) is set to below value or higher, the inverter is sure to be necessary to derate their nominal current.

Description

Fuji 4-pole standard motor

Rated capacity is calculated by assuming the output rated voltage as 440 V.

Output voltage cannot exceed the power supply voltage.

When the carrier frequency (F26) is set to below value or higher, the inverter is sure to be necessary to derate their nominal current.

When the carrier frequency (F26) is set to below value or higher, the inverter is sure to be necessary to derate their nominal current.
HHD spec.— type 0002 to 0012:8kHz, type 0022 to 0168:10kHz, type 0203 to 0590:6kHz
HND spec.— type 0002 to 0012:8kHz, type 0022 to 0059:10kHz, type 0072 to 0168:6kHz, type 0203 to 0590:4kHz
HD,ND spec.— All type : 4kHz

The rated output current at HD/ND spec. is decreased 2% for every 1 °C (1.8 °F) when ambient temperature is +40 °C (+104 °F) or more.
The value is calculated assuming that the inverter is connected with a power supply with the capacity of 500 kVA
(or 10 times the inverter capacity if the inverter capacity exceeds 50 kVA) and %X is 5%.
Be sure to use the DCR when applicable motor capacity is 75kW or above.
Obtained when a DC reactor (DCR) is used.
Average braking torque for the motor running alone. (It varies with the efficiency of the motor.)
Voltage unbalance (%) =(Max. voltage (V) – Min. voltage (V))/Three -phase average voltage (V) × 67 (IEC 61800 – 3) If this value is 2 to 3%, use an optional AC reactor (ACR).

The EMC Filter Built-in Type supports only a product for EU.
S: Standard (basic type), E: EMC filter built-in type (0059 to 0590)
HND spec. of the type 0007 and 0012: allowable ambient temperature 40 °C (+104 °F) or less.
The rated output current at HND spec. is decreased 1% for every 1 °C (1.8 °F) when ambient temperature is +40 °C (+104 °F) or more.
CAN terminal, 1 analog current output